Selection Guide

Domestic selection guide

These recommendations are based on the guidelines in BS 6700. Guidance should be sought for unusual applications, e.g.high flow-rate showers, large baths etc.

Hot water demand Bedrooms Indirect units Direct units
1 Standard bath or shower Bedsit/1 bed
2-3 bed
3-4 bed
120
120
150
150
180
210
1 Standard bath 2-3 bed
3-4 bed
120
120
210
210
1 Bath and En-suite 2-3 bed
3-4 bed
4-5 bed
150
150
180
210
210
250
2 Standard baths 2-3 bed
3-4 bed
4-5 bed
180
180
210
210
210
250
3 Bathrooms 3-4 bed
4-5 bed
5-6 bed
250
250
300
300
300
300

Domestic selection guide

These recommendations are based on the guidelines in BS 6700. Guidance should be sought for unusual applications, e.g.high flow-rate showers, large baths etc.

Typical commercial application Indirect units
Large house - 6 bed/4 bathrooms 2 x 210
Guest house - 8 bed/4 bathrooms 2 x 300
Small hotel - 8 bed/8 bathrooms 3 x 210
Sports pavillion (25 people/4 showers) 2 x 300
Sports pavillion (25 people/6 showers) 3 x 210
Student house (25 people/3 bathrooms) 3 x 300
Old peoples' home (60 beds/10 bathrooms) 5 x 300 each supplying 2 bathrooms

Immersion heaters

Size Direct Indirect
120 litre 2 x 3 kW Immersion heaters 1 x 3 kW Immersion heaters
150 litre 2 x 3 kW Immersion heaters 1 x 3 kW Immersion heaters
180/210 litre 2 x 3 kW Immersion heaters 1 x 3 kW Immersion heaters
250/300 litres 2 x 3 kW Immersion heaters 2 x 3 kW Immersion heaters

Example illustration.

A school swimming pool has 5 showers in each of two changing rooms. The shower heads are flow-restricted to 9 litres per minute (2Ú3 of this will be hot water). Usually there are 3 one hour lessons each morning and three each afternoon. Assuming a class size of 30 children.

Maximum demand = 10 shower heads x 9 litres/min = 90 litres/min. This is more than one Ultrasteel can supply. At least two Ultrasteels will be needed to provide this. Total demand = 30 children x 6 litres/minute x 5 minute shower each = 900 litres 3x300 litre units will be required.

Reheat time has to be a maximum of one hour so it is reheated in time for the next lesson. A CUI 300 can reheat its entire contents in 60 minutes with a boiler power of 15kW. So total boiler power required = 45kW. If direct units were used they would have to be fitted with immersion heaters rated at 15kW (typically 1 x 9kW + 1 x 6 kW)